Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10CM00727
Parcel: 13628005V

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00727
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
03/23/2010 BIANCA RAMIREZ ENGINEERING REVIEW Approved
03/24/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/24/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the ventilation calculations; the area served by HP-16 and identified as "office" appears to be a telecommunications area. Reference: Sections 403.3 and 403.3.2, IMC 2006.
2. Revise the calculations to show that the common ventilation system is sized in accordance with Section 403.3.2, IMC 2006.
03/24/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/24/2010 ROBERT SHERRY WATER REVIEW Approved
03/24/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/24/2010 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
03/24/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/24/2010 ERIC NEWCOMB ADA REVIEW Passed
03/24/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
03/25/2010 DAVE MANN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/06/2010 DELMA ROBEY OUT TO CUSTOMER Completed