Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/23/2010 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
03/23/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
03/24/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
03/24/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the ventilation calculations; the area served by HP-16 and identified as "office" appears to be a telecommunications area. Reference: Sections 403.3 and 403.3.2, IMC 2006. 2. Revise the calculations to show that the common ventilation system is sized in accordance with Section 403.3.2, IMC 2006. |
03/24/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/24/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/24/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
03/24/2010 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
03/24/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
03/24/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
03/24/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
03/25/2010 | DAVE MANN | FIRE | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/06/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |