Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM00721
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/27/2010 | CLAYTON TREVILLYAN | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS Date: 5-27-10 Activity: T10CM00721 2nd review Address: 3232 E. Elida St. Applicant: Joseph Lovallo Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval. GENERAL REQUIREMENTS: 1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. SECTIONS - DETAILS: 2. Provide revised detail sheet A2 3. Specify hardware connection of post to beam on detail 5-A2 4. Clarify all ledger sizes (12x10?) 5. Specify height of stucco weep screed above grade with a min. clearance 4" above grade or 2" above paved areas, R703.6.2.1. 6. All footings must extend a minimum of 12" below grade (including porch footings) , R403.1.6. PLUMBING PLAN: 7. Include range in gas demand schedule. ELECTRICAL PLAN: 8. Convenience receptacles and light switches/fixtures shall be provided within 25' of mechanical equipment (condensing unit outside), E3801.11, E3803.4. OUTDOOR LIGHTING CODE 9. Only fully shielded fixtures located under a roof are exempt. Specify fully shielded fixtures and provide cut sheets. 10. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style). If you have any questions please contact: Clayton Trevillyan 520.837.4913 Residential Plan Review |