Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM00713
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/08/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/12/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET S-1.0 (SITE PLAN); SHEET A-1.0 (BUILDING PLAN): SHEET S-1.0 INDICATES THE NEW ADDITION IS "CAFETERIA" WITH 1159 SF, WHILE SHEET A-1.0 INDICATES "MULTI-PURPOSE CLASSROOM" WITH 1102 SF. CLARIFY. 2. SHEET A-1.0; OCCUPANCY TABULATION: THIS TABLE INDICATES IT IS NEW CONSTRUCTION FOR BUILDING #2, BUT INCLUDES THE MULTI-PURPOSE CLASSROOM ADDITION, WHICH IS INDICATED AS BUILDING #1. CLARIFY. 3. SHEET S1: THE GENERAL STRUCTURAL NOTES REFERENCE A SOILS REPORT. PROVIDE THIS REPORT FOR REVIEW. 4. SHEET S2; PLAN: CHANGE THE PLAN TITLE TO FOUNDATION PLAN. 5. SHEET S2; CAFETERIA ADDITION: CHANGE THE SECTION CUT 1/S3.0. 6. SHEET S3; PLAN: CHANGE THE PLAN TITLE TO ROOF FRAMING PLAN. 7. SHEET S4; SECTION 4: CHANGE THE SECTION TITLE. 8. SHEET S5; SECTION 5: PROVIDE TEXT OF HOW THE TAPERED 2X CRICKET FRAMING IS CONNECTED TO THE EXISTING ROOF. 9. GENERAL: ALL DEFERRED SUBMITTALS MUST BE APPROVED BY LEERAY HANLY BEFORE BEING SUBMITTED. 10. STRUCTURAL CALCULATIONS: DID NOT LOCATE IN THE LATERAL CALCULATIONS THE REQUIRED NAILING SIZE AND SPACING AT THE ROOF PLYWOOD OR SHEARWALL PLYWOOD. PROVIDE. 11. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
04/13/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
04/13/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
04/20/2010 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide a reduced pressure backflow assembly to protect the city water supply from the new building. Reference: City of Tucson Ordinance 9976, Backflow Prevention and Cross-connection Control. |
04/20/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006. 2. Show that the floor of the restroom slopes toward the floor drain. Reference: Section 411.2, UPC 2006. 3. Provide a CW shut off valve for the building entrance. Reference: Section 605.2, UPC 2006. 4. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006. 5. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. Reference: Section 609.10, UPC 2006. 6. Revise the size of the gutters to comply with the requirements of Section 1106.3, UPC 2006. Refer also to Section 1106.4, UPC 2006. 7. Clarify the slope of the gutters as shown on sheet A-2.0; it appears that the drawing calls for the gutters to slope away from some of the downspouts. |
04/20/2010 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | Plans will be approved when the site plan is approved. |
04/20/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (3), IMC 2006. 2. Provide energy code compliance calculations using the correct climate zone (Pima County < 4,000 feet) and the correct code (2006 IECC). (Note that the Mechanical Compliance Certificate shown on sheet M2.1 uses the 2009 IECC and is for Phoenix, AZ.) Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006. 3. Provide the cooling and heating load calculations used to justify the size of the heat pumps. Reference: Section 503.2.1, IECC 2006. |
04/21/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
04/21/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/23/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
04/23/2010 | SUE REEVES | REJECT SHELF | Completed |