Permit Number: T10CM00713
Parcel: 13815014G

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00713
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2010 MARTIN BROWN FIRE REVIEW Approved
04/12/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S-1.0 (SITE PLAN); SHEET A-1.0 (BUILDING PLAN): SHEET S-1.0 INDICATES THE NEW ADDITION IS "CAFETERIA" WITH 1159 SF, WHILE SHEET A-1.0 INDICATES "MULTI-PURPOSE CLASSROOM" WITH 1102 SF. CLARIFY.
2. SHEET A-1.0; OCCUPANCY TABULATION: THIS TABLE INDICATES IT IS NEW CONSTRUCTION FOR BUILDING #2, BUT INCLUDES THE MULTI-PURPOSE CLASSROOM ADDITION, WHICH IS INDICATED AS BUILDING #1. CLARIFY.
3. SHEET S1: THE GENERAL STRUCTURAL NOTES REFERENCE A SOILS REPORT. PROVIDE THIS REPORT FOR REVIEW.
4. SHEET S2; PLAN: CHANGE THE PLAN TITLE TO FOUNDATION PLAN.
5. SHEET S2; CAFETERIA ADDITION: CHANGE THE SECTION CUT 1/S3.0.
6. SHEET S3; PLAN: CHANGE THE PLAN TITLE TO ROOF FRAMING PLAN.
7. SHEET S4; SECTION 4: CHANGE THE SECTION TITLE.
8. SHEET S5; SECTION 5: PROVIDE TEXT OF HOW THE TAPERED 2X CRICKET FRAMING IS CONNECTED TO THE EXISTING ROOF.
9. GENERAL: ALL DEFERRED SUBMITTALS MUST BE APPROVED BY LEERAY HANLY BEFORE BEING SUBMITTED.
10. STRUCTURAL CALCULATIONS: DID NOT LOCATE IN THE LATERAL CALCULATIONS THE REQUIRED NAILING SIZE AND SPACING AT THE ROOF PLYWOOD OR SHEARWALL PLYWOOD. PROVIDE.
11. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
04/13/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
04/13/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
04/20/2010 ROBERT SHERRY WATER REVIEW Denied Provide a reduced pressure backflow assembly to protect the city water supply from the new building. Reference: City of Tucson Ordinance 9976, Backflow Prevention and Cross-connection Control.
04/20/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
2. Show that the floor of the restroom slopes toward the floor drain. Reference: Section 411.2, UPC 2006.
3. Provide a CW shut off valve for the building entrance. Reference: Section 605.2, UPC 2006.
4. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006.
5. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. Reference: Section 609.10, UPC 2006.
6. Revise the size of the gutters to comply with the requirements of Section 1106.3, UPC 2006. Refer also to Section 1106.4, UPC 2006.
7. Clarify the slope of the gutters as shown on sheet A-2.0; it appears that the drawing calls for the gutters to slope away from some of the downspouts.
04/20/2010 LOREN MAKUS ENGINEERING REVIEW Denied Plans will be approved when the site plan is approved.
04/20/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (3), IMC 2006.
2. Provide energy code compliance calculations using the correct climate zone (Pima County < 4,000 feet) and the correct code (2006 IECC). (Note that the Mechanical Compliance Certificate shown on sheet M2.1 uses the 2009 IECC and is for Phoenix, AZ.) Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
3. Provide the cooling and heating load calculations used to justify the size of the heat pumps. Reference: Section 503.2.1, IECC 2006.
04/21/2010 GERRY KOZIOL WWM REVIEW Approved
04/21/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/23/2010 DELMA ROBEY OUT TO CUSTOMER Completed
04/23/2010 SUE REEVES REJECT SHELF Completed