Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T10CM00694
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/24/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET C4; DETAIL 3: THE POST SIZE IS NOT INDICATED IN THE DRAWINGS. PROVIDE. 2. SHEET C4; DETAIL 4: PROVIDE STRUCTURAL CALCULATIONS FOR THE POST AND FOUNDATION DESIGN. 3. GENERAL: PROVIDE RESPONSES TO ALL REVIEW COMMENTS. |
| 04/01/2010 | Michael Wyneken | PLANNING-CITY HALL | REVIEW | Denied | Add comment regarding painting metal screen panels, per condition. |
| 04/01/2010 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: T10CM00694 Cell Tower (1st Review) TRANSMITTAL DATE: April 1, 2010 1. The Cell Tower plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning has reviewed the plan and it appears that it meets all LUC and D.S. requirements. Once all PDSD agencies have approved the plan Zoning will approve the plan. 3. Zoning will re-review the Cell Tower plan on the next submittal to insure compliance with the approved Special Exception process. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\celltower\t10cm00694.doc |
| 04/05/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/09/2010 | BRIAN HEFFERNAN | COMMUNICATIONS | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/20/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 04/20/2010 | SUE REEVES | REJECT SHELF | Completed |