Permit Number: T10CM00667
Parcel: 119421820

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00667
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2010 DAVE MANN FIRE REVIEW Approved
03/24/2010 GERRY KOZIOL WWM REVIEW Approved
04/01/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
04/05/2010 ROBERT SHERRY WATER REVIEW Approved
04/06/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide auxiliary drain pans or secondary drain systems for the fan coil units. Reference: Section 307.2.3 IMC 2006.
2. Provide information on the sequence of operation for the restroom exhaust fan to show that all of the air supplied to the restroom will be exhausted. Reference: Section 403.2.1 (3), IMC 2006.
3. Show the size, route, and termination of the dryer exhaust duct. Reference: Sections 504.1, 504.2, and 504.4, IMC 2006.
4. Provide energy code compliance calculations for the building envelope and the mechanical equipment. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
04/06/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the site plan referenced in the waste and vent diagram and in the water isometric. Reference: Section 103.2.3, UPC 2006.
2. Clarify the design of the "water filter bypass" (keynote # 3, sheet P3). Reference: Section 103.2.3, UPC 2006.
3. Clarify the design for the recirculated hot water piping at the water heater, including the recirculating pump and valves (i.e. provide a detail). Reference: Section 103.2.3, UPC 2006.
4. Provide listing information for the Gleco plaster trap. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). Reference: Section 301.1.1, UPC 2006.
5. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Clarify how the shelf is to be attached to the wall. Reference: Sections 310.0 and 314.5, UPC 2006.
6. Appliances (e.g. ultrasonic cleaner, sterilizer, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.
7. Revise the water pressure and fixture unit calculations to provide a minimum water pressure of 25 PSI (per shell drawings) and use the water fixture units per Table 6-5 or Table A-2 (Clothes washer = 4.0 FU, Lab sinks = 2 FU).
8. Show that the termination of the plumbing vents complies with the requirements of Section 906.1, UPC 2006 with respect to the clearance from walls or parapets.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/08/2010 DELMA ROBEY OUT TO CUSTOMER Completed
04/08/2010 SUE REEVES REJECT SHELF Completed