Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10CM00603
Parcel: 110091030

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - RES

Permit Number - T10CM00603
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2010 MICHAEL ST. PAUL ZONING REVIEW Denied P&DS TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T10CM00603
2911 North Cloverland Avenue
Addition and detached sleeping quarters for SFR


TRANSMITTAL: April 5, 2010


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO).


This Site requires a DDO for the setback to the south property line. This site is in the R-1 Zone (LUC Section 2.3.4.2.A.1). The Development Designator is "G" (LUC Section 3.2.3.1.B) and the Perimeter Yard Indicator AA (LUC Section 3.2.6.4).

The minimum setback to the south property line is the greater of six feet or two-thirds the height of the structure's wall facing the property line. The minimum setback to the south property line is six (6) feet. The proposed setback is four (4) feet. to the SFR and four (4) feet four (4) inches to the detached sleeping quarters.
04/05/2010 MICHAEL ST. PAUL NPPO REVIEW Passed
05/14/2010 CPIERCE1 ENGINEERING REVIEW Needs Review
05/14/2010 CPIERCE1 BUILDING-RESIDENTIAL REVIEW Needs Review