Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10CM00578
Parcel: 10511043B

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T10CM00578
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved