Permit Number: T10CM00578
Parcel: 10511043B

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T10CM00578
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the ventilation calculations for FC-1 and FC-2 to take into account the different occupancy loads in the respective spaces served by the two fan coils. Reference: Sections 403.3 and 403.3.2, IMC 2006.