Permit Number: T10CM00578
Parcel: 10511043B

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T10CM00578
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the ventilation calculations to include the conference room (224) and the weapons cleaning room (221). Reference: Sections 403.3 and 403.3.2, IMC 2006.
2. Positively pressurized exhaust ducts may not pass through a plenum. Reference: Section 601.4, IMC 2006.
07/27/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved