Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T10CM00578
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/27/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the ventilation calculations to include the conference room (224) and the weapons cleaning room (221). Reference: Sections 403.3 and 403.3.2, IMC 2006. 2. Positively pressurized exhaust ducts may not pass through a plenum. Reference: Section 601.4, IMC 2006. |
07/27/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/30/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |