Permit Number: T10CM00575
Parcel: 11007232A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00575
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2010 DAVID RIVERA ZONING REVIEW Approved
03/09/2010 BIANCA RAMIREZ ENGINEERING REVIEW Approved
03/09/2010 ERIC NEWCOMB ADA REVIEW Passed
03/09/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A6; SECTIONS 8 AND 9: CHECK HEIGHT OF COUNTER/SINK TO MEET ACCESSIBILITY REQUIREMENTS.
2. SHEET A3; SHEET A8 (ROOM FINISH SCHEDULE): THE INFILL OF THE WALL ALONG THE CORRIDOR 204 ALONG WITH THE NEW DOORS IN THE CORRIDOR MUST BE FIRE RATED (EXIT CORRIDOR). VERIFY AND INDICATE.
3. EXPLAIN HOW THE FIRE RESISTANCE RATING OF THE EXIT CORRIDOR IS TO BE MAINTAINED (CORRIDOR IS OPEN TO THE LOBBY AND OFFICE AREA).
03/09/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
03/09/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/11/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the revisions to the ductwork for HP-7 will be modified to maintain the fire rating of the exit corridor.
2. Clarify the condensate drainage from DS-A with regard to size and termination. A pumped waste may not have a direct connection with the plumbing system. reference; Section 814.1, UPC 2006.
03/11/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/11/2010 ROBERT SHERRY WATER REVIEW Approved
03/11/2010 MARTIN BROWN FIRE REVIEW Denied Fire Comments:

Exit corridor must maintain fire rating. Door and sidelights 200A and 204A must be self closing with 20 min. rating. Wall tye 2 on Sheet A3 between corridor and hall 204 must be one hour rated. See IFC Section 1017.
03/11/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/23/2010 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/23/2010 DELMA ROBEY OUT TO CUSTOMER Completed