Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM00575
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/09/2010 | DAVID RIVERA | ZONING | REVIEW | Approved | |
03/09/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
03/09/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
03/09/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A6; SECTIONS 8 AND 9: CHECK HEIGHT OF COUNTER/SINK TO MEET ACCESSIBILITY REQUIREMENTS. 2. SHEET A3; SHEET A8 (ROOM FINISH SCHEDULE): THE INFILL OF THE WALL ALONG THE CORRIDOR 204 ALONG WITH THE NEW DOORS IN THE CORRIDOR MUST BE FIRE RATED (EXIT CORRIDOR). VERIFY AND INDICATE. 3. EXPLAIN HOW THE FIRE RESISTANCE RATING OF THE EXIT CORRIDOR IS TO BE MAINTAINED (CORRIDOR IS OPEN TO THE LOBBY AND OFFICE AREA). |
03/09/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
03/09/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
03/11/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the revisions to the ductwork for HP-7 will be modified to maintain the fire rating of the exit corridor. 2. Clarify the condensate drainage from DS-A with regard to size and termination. A pumped waste may not have a direct connection with the plumbing system. reference; Section 814.1, UPC 2006. |
03/11/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
03/11/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/11/2010 | MARTIN BROWN | FIRE | REVIEW | Denied | Fire Comments: Exit corridor must maintain fire rating. Door and sidelights 200A and 204A must be self closing with 20 min. rating. Wall tye 2 on Sheet A3 between corridor and hall 204 must be one hour rated. See IFC Section 1017. |
03/11/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
03/23/2010 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/23/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |