Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM00574
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/09/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1.0; ELEVATIONS 1 AND 2: PLEASE CHECK HEIGHT OF COUNTER/SINK AREA TO MEET ACCESSIBILITY REQUIREMENTS. |
| 03/09/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 03/09/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 03/09/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/09/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 03/10/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the ventilation calculations to include all of the areas served by AC-1 and include an air distribution effectiveness value of 0.8 (ceiling supply, ceiling return, warm air greater than 15 degrees Fahrenheit above space temperature). Reference: Section 6.2.2.2, ASHRAE Standard 62.1-2004. 2. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson. 3. Show the size, routing, and termination of the condensate drain. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006. 4. Provide a Type I hood over all domestic cooking appliances used for commercial purposes. Reference: Section 507.2.3, IMC 2006. 5. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top unit. Reference: Section 302.1, IMC 2006. |
| 03/10/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/10/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/10/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a cleanout for the new sink. Reference: section 707.4, UPC 2006. 2. Provide architectural/structural details to show how the water heater is to be supported and accessed in the ceiling space. Confirm that detail 1/P2 shows how it is to be mounted; what is the construction of the wll to which it is being connected. |
| 03/24/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 03/24/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 03/24/2010 | MARTIN BROWN | FIRE | REVIEW | Approved |