| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/09/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Electrical Plans denied for the following: 1. Provide a fixture schedule. 2. Provide circuitry for lighting. 3. Provide Light Budget calculations per 2006 IECC> 4. Providse a one line diagram for service and panels showing voltage, loads and location. Ray T Majuta PDSD, City of Tucson 4/9/10 520/837/4988 |