Permit Number: T10CM00562
Parcel: 13313005E

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T10CM00562
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2010 DAVE MANN FIRE REVIEW Approved
03/16/2010 STEVE SHIELDS ZONING REVIEW Approved
03/16/2010 Michael Wyneken PLANNING-CITY HALL REVIEW Approved To applicant:

This application was incomplete. The Special Exception Approval LLetter was not supplied as stipularted under condition c. I provided it this time. I do not have the time to comp[lete submittals. Future incomplete submittals will be rejected. MW.
03/17/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET D-06 (DETAIL D04); STRUCTURAL CALCULATIONS (SHEET R1/R4): THE STRUCTURAL CALCULATIONS INDICATE AN 8'-0" WALL HEIGHT ABOVE GRADE, WHILE THE DRAWING INDICATES 10'-0" MAXIMUM. CLARIFY AND REVISE.
2. SHEET D-06; DETAIL D04: IF THE 10' TALL WALL DESIGN IS USED, IS THE STRUCTURAL ENGINEER OF RECORD ALLOWING THE SPECIAL INSPECTION OF THE MASONRY WALL TO BE WAIVED? VERIFY.
3. SHEET D-13 (DETAIL 5); STRUCTURAL CALCULATIONS (SHEET 12): THE STRUCTURAL CALCULATIONS INDICATE A 2 1/2" DIAMETER STANDARD PILE COLUMN, BUT THE DRAWINGS DO NOT STATE THE COLUMN SIZE. REVISE.
4. SHEET D-13; DETAIL 5: IN THE LOWER DETAIL, THE SUPPORT ANGLE IS REFERENCED AS 6" LONG, WHILE THE UPPER DETAIL INDICATES A 3 1/2" LENGTH. REVISE.
5. SHEET D-13 (FABRIC SUPPORT PLAN); STRUCTURAL CALCULATIONS (SHEET 15A): THE STRUCTURAL CALCULATIONS INDICATE A FOOTING AT THE SUPPORT POST, BUT NO FOOTING IS INDICATED ON THE DRAWING. VERIFY.
6. GENERAL: A MINIMUM LETTERING HEIGHT OF 3/32" IS REQUIRED ON ALL SHEETS (SEE SHEETS D-12 AND GS57631).
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/23/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM00562
7575 E Speedway Bl, Cell Tower

Electrical plans denied for the following:

1. Plan shows a 3 phase 277/480 volt system feeding a 50 kva transformer, changing the systen to a 120/240 volt system 1 phase, incorrect wiring---- redo drawing.
2. List following conductor and conduit size runs,
a. meter to main disconnect
b. transformer to panel POPB.

Ray T Majuta
Elect Plan Review
PDSD, City of Tucson
Ray.Majuta@tucsonax.gov
04/05/2010 BRIAN HEFFERNAN COMMUNICATIONS REVIEW Approved need communications information form

Final Status

Task End Date Reviewer's Name Type of Review Description
04/14/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
04/14/2010 SUE REEVES REJECT SHELF Completed