Permit Number: T10CM00544
Parcel: 12218257A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM00544
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2010 RONALD BROWN ZONING HC REVIEW Approved
04/26/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approv-Cond Conditional approval provided for Deferred Submittals letter to LeeRay Hanly.
04/27/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved; the building drawings do not show the same amount of insulation for the roof and walls as is shown in the calculations. Revise the energy code analysis, coordinating the building components used in the analysis with those shown on the drawing. Reference: Section 502, IECC 2006, as amended by the City of Tucson.
04/27/2010 ROBERT SHERRY WATER REVIEW Approved
04/27/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide vent piping of sufficient size to comply with Section 904.1, UPC 2006. Vents located upstream from pumps, ejectors, backwater valves, or other devices that obstruct the free flow of gases between the building sewer and the outside atmosphere shall not be used for meeting the required cross-sectional vent area.
2. Provide roof drainage for the walk-in coolers. All roof areas shall be drained by roof drains, scuppers, or gutters. Reference: Section 1101.11.1, UPC 2006.
3. The roof scupper draining area 4 (1046 SF) is undersized and lacks any overflow capacity. See Section 1101.11.2.1 for sizing information of roof scuppers. Reference: Section 1101.11, UPC 2006.
4. Clarify the termination of the roof drain and overflow drain. Show the roof drain and overflow drain on the roof plan.
04/27/2010 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Denied Plans denied for the following:

1. Provide electrical distribution system capable of interrupting available fault current. 2005 NEC 110.9. If using series rating provide information required by 2005 NEC 110.22 and 240.86(A) or 240.86(B).

2. None of the loads on panel K2 can be considered as kitchen equipment and NEC 250.56 does not apply. See comment #3 from previous review comments.

Rich Jiroudek
Elect Plns Exmn
520-954-0161

Final Status

Task End Date Reviewer's Name Type of Review Description
04/29/2010 CPIERCE1 OUT TO CUSTOMER Completed
04/29/2010 CPIERCE1 REJECT SHELF Completed