Permit Number: T10CM00541
Parcel: 12710084B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00541
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
03/15/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/15/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/15/2010 ROBERT SHERRY WATER REVIEW Approved
03/15/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET a1: FLOOR PLAN: PER IBC SECTION 2902.4, THE ACCESSIBLE ROUTE TO THE RESTROOM AND DRINKING FOUNTAIN MAY NOT PASS THROUGH A STORAGE ROOM. VERIFY.
03/15/2010 GBONILL1 WWM REVIEW Needs Review
03/15/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The minimum trap/traparm size for a service sink is 2".
2. The minimum waste line size for a sink is 2".
3. A service sink (3 DFU) may not be the upper fixture in a vertical wet vent.
03/15/2010 GBONILL1 ENGINEERING REVIEW Needs Review
03/15/2010 DAVE MANN FIRE REVIEW Approved
03/15/2010 ERIC NEWCOMB ADA REVIEW Passed
03/15/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/15/2010 ERIC NEWCOMB ZONING HC REVIEW Denied SEE BUILDING COMMENT.