Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM00541
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/05/2010 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
03/15/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
03/15/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
03/15/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/15/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET a1: FLOOR PLAN: PER IBC SECTION 2902.4, THE ACCESSIBLE ROUTE TO THE RESTROOM AND DRINKING FOUNTAIN MAY NOT PASS THROUGH A STORAGE ROOM. VERIFY. |
03/15/2010 | GBONILL1 | WWM | REVIEW | Needs Review | |
03/15/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The minimum trap/traparm size for a service sink is 2". 2. The minimum waste line size for a sink is 2". 3. A service sink (3 DFU) may not be the upper fixture in a vertical wet vent. |
03/15/2010 | GBONILL1 | ENGINEERING | REVIEW | Needs Review | |
03/15/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
03/15/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
03/15/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
03/15/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Denied | SEE BUILDING COMMENT. |