Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM00538
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/05/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1.0; ENLARGED RESTROOM PLAN: REVISE PLAN TO MEET ACCESSIBILITY REQUIREMENTS PER ICC/ANSI A117.1-2003, FIGURE 604.3. 2. GENERAL: PROVIDE LATERAL BRACING TO TOP OF NEW INTERIOR PARTITION WALLS TO MEET IBC SECTION 1607.13 REQUIREMENTS FOR LATERAL LOADS. PROVIDE DETAILS ON DRAWINGS INDICATING BRACING SIZE AND SPACING, CONNECTION OF BRACING TO EXISTING STRUCTURE ABOVE, AND CONNECTION OF BRACING TO TOP OF NEW WALL. |
| 03/05/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 03/05/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/05/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 03/08/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | ASHRAE 62.1-2004 is authorized for use in calculating the outside air quantities in lieu of the method shown in Section 403.3, IMC 2006 but recirculation of the air supplied to the nail area is prohibited and the exhaust for the nail areas is required to capture the contaminants at the source. Reference: sections 403.2.1 and Table 403.3 (footnote i), IMC 2006. |
| 03/08/2010 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 03/08/2010 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide the size of the water meter serving the nail salon and indicate the total demand on the meter. |
| 03/08/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T10CM00538 1925 E GRANT RD ELECTRICAL PLANS DENIED FOR THE FOLLOWING: 1. NO RISER DIAGRAM WITH PLANS. 2. A-10 ON PLAN RECEPTACLES, ON SCHEDULE ONE PHASE OF AC. 3. A-12 ON PLAN RECEPTACLES,ON SCHEDULE ONE PHASE OF AC. 4.A-14 ON PLAN RECEPTACLES, ON SCHEDULE ONE PHASE OF WH. 5. A-14,16 NOT SHOWN ON PLAN. RT MAJUTA EL PLN CK 3/8/10, CITY OF TUCSON, 520/837/4899 |
| 03/08/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 03/08/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
| 03/08/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Each piece of equipment (e.g. pedicure chair units) requiring backflow protection shall be independently protected. Reference: Section 603.0, UPC 2006, as amended by the City of Tucson. 2. Indicate the location of the upper terminal cleanout the serves the existing 4" building drain. Reference: Sections 103.2.3 and 707.4, UPC 2006. 3. The waste fixture unit value for a floor sink is dependent upon the fixtures or appliances draining into the floor sink. The pedicure chair units each have two waste fixture units. Revise the waste and vent piping as needed. |
| 03/10/2010 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/10/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |