Permit Number: T10CM00538
Parcel: 112062820

Address:
1925 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00538
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.0; ENLARGED RESTROOM PLAN: REVISE PLAN TO MEET ACCESSIBILITY REQUIREMENTS PER ICC/ANSI A117.1-2003, FIGURE 604.3.
2. GENERAL: PROVIDE LATERAL BRACING TO TOP OF NEW INTERIOR PARTITION WALLS TO MEET IBC SECTION 1607.13 REQUIREMENTS FOR LATERAL LOADS. PROVIDE DETAILS ON DRAWINGS INDICATING BRACING SIZE AND SPACING, CONNECTION OF BRACING TO EXISTING STRUCTURE ABOVE, AND CONNECTION OF BRACING TO TOP OF NEW WALL.
03/05/2010 ERIC NEWCOMB ADA REVIEW Passed
03/05/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/05/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
03/08/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied ASHRAE 62.1-2004 is authorized for use in calculating the outside air quantities in lieu of the method shown in Section 403.3, IMC 2006 but recirculation of the air supplied to the nail area is prohibited and the exhaust for the nail areas is required to capture the contaminants at the source. Reference: sections 403.2.1 and Table 403.3 (footnote i), IMC 2006.
03/08/2010 TERRY STEVENS ZONING REVIEW Approved
03/08/2010 ROBERT SHERRY WATER REVIEW Denied Provide the size of the water meter serving the nail salon and indicate the total demand on the meter.
03/08/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T10CM00538
1925 E GRANT RD


ELECTRICAL PLANS DENIED FOR THE FOLLOWING:

1. NO RISER DIAGRAM WITH PLANS.
2. A-10 ON PLAN RECEPTACLES, ON SCHEDULE ONE PHASE OF AC.
3. A-12 ON PLAN RECEPTACLES,ON SCHEDULE ONE PHASE OF AC.
4.A-14 ON PLAN RECEPTACLES, ON SCHEDULE ONE PHASE OF WH.
5. A-14,16 NOT SHOWN ON PLAN.

RT MAJUTA
EL PLN CK
3/8/10, CITY OF TUCSON,
520/837/4899
03/08/2010 BIANCA RAMIREZ ENGINEERING REVIEW Approved
03/08/2010 DAVE MANN FIRE REVIEW Approved
03/08/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Each piece of equipment (e.g. pedicure chair units) requiring backflow protection shall be independently protected. Reference: Section 603.0, UPC 2006, as amended by the City of Tucson.
2. Indicate the location of the upper terminal cleanout the serves the existing 4" building drain. Reference: Sections 103.2.3 and 707.4, UPC 2006.
3. The waste fixture unit value for a floor sink is dependent upon the fixtures or appliances draining into the floor sink. The pedicure chair units each have two waste fixture units. Revise the waste and vent piping as needed.
03/10/2010 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/10/2010 DELMA ROBEY OUT TO CUSTOMER Completed