Permit Number: T10CM00532
Parcel: 13323193C

Address:
750 N KOLB RD

Review Status: Completed

Review Details: OTHER

Permit Number - T10CM00532
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The submitted drawings do not appear to show the actual scope of plumbing work. Provide complete, sealed, plumbing drawings for the new work along with a reference copy of the last permitted drawings for the building.
2. All plumbing fixtures and all appliances directly connected to the plumbing system shall be specified.
03/11/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Third request; comment not addressed. Provide sealed mechanical drawings to show the extent of new work. Provide complete, sealed, mechanical drawings for the new work along with a reference copy of the last permitted drawings for the building. Structural details and calculations shall be provided to show how the new hood is to be connected to the building structure.
03/16/2010 DROBEY1 WWM REVIEW Needs Review