Permit Number - T10CM00532
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The submitted drawings do not appear to show the actual scope of plumbing work. Provide complete, sealed, plumbing drawings for the new work along with a reference copy of the last permitted drawings for the building. 2. All plumbing fixtures and all appliances directly connected to the plumbing system shall be specified. |
| 03/11/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Third request; comment not addressed. Provide sealed mechanical drawings to show the extent of new work. Provide complete, sealed, mechanical drawings for the new work along with a reference copy of the last permitted drawings for the building. Structural details and calculations shall be provided to show how the new hood is to be connected to the building structure. |
| 03/16/2010 | DROBEY1 | WWM | REVIEW | Needs Review |