Permit Number: T10CM00532
Parcel: 13323193C

Address:
750 N KOLB RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00532
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2010 STEVE SHIELDS ZONING REVIEW Approved
03/04/2010 JASON GREEN ENGINEERING REVIEW Approved
03/05/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/05/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide sealed mechanical drawings to show the extent of new work.
03/05/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/05/2010 ROBERT SHERRY WATER REVIEW Approved
03/05/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The minimum size for a sink drain is 2"; provide a wet vent section that complies with Section 908.2, UPC 2006. Reference: footnote 2, Table 7-3, UPC 2006.
2. If a floor drain is desired in the bar area, provide trap seal protection. Reference: Sections 1007.0 and 1007.1, UPC 2006, as amended by the City of Tucson.
3. Provide fixture descriptions for all plumbing fixtures. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). Reference: Sections 301.1.1 and 401.1, UPC 2006.
03/05/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/05/2010 ERIC NEWCOMB ADA REVIEW Passed
03/05/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
03/10/2010 CPIERCE1 WWM REVIEW Needs Review
03/10/2010 MARTIN BROWN FIRE REVIEW Approved