Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM00532
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/04/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 03/04/2010 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 03/05/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/05/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide sealed mechanical drawings to show the extent of new work. |
| 03/05/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/05/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/05/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The minimum size for a sink drain is 2"; provide a wet vent section that complies with Section 908.2, UPC 2006. Reference: footnote 2, Table 7-3, UPC 2006. 2. If a floor drain is desired in the bar area, provide trap seal protection. Reference: Sections 1007.0 and 1007.1, UPC 2006, as amended by the City of Tucson. 3. Provide fixture descriptions for all plumbing fixtures. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). Reference: Sections 301.1.1 and 401.1, UPC 2006. |
| 03/05/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/05/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 03/05/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 03/10/2010 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 03/10/2010 | MARTIN BROWN | FIRE | REVIEW | Approved |