Permit Number: T10CM00516
Parcel: 129041750

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM00516
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
04/12/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied ProjectT:10CM00516, 2050 E Broadway
Solar Photovoltaic Sysrem

1.Last comments requested for electrical plan to show the size and run of the grounding electrode conductor from the main service to the Inverters per 2005 NEC 690.47.
The feeder from the 400 amp CT can to the main photovoltaic AC disconnect shows a 1/0 GRD, then a #8 cu GRD taken to each inverter.
I beleive this is actually for the use of an equipment ground rather than a grounded electrode conductor, or the same conductor being used for both. There should be two individual conductors one for each.


Ray T Majuta
PDSD, City of Tucson,
Elect Pln Review,
4/8/10
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
04/13/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
04/13/2010 SUE REEVES REJECT SHELF Completed