Permit Number: T10CM00516
Parcel: 129041750

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T10CM00516
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2010 DAVE MANN FIRE REVIEW Approved
03/26/2010 RONALD BROWN ZONING HC REVIEW Passed
03/26/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied Please provide structural calculations for the additional load added to the existing roof framing system. Decsribe fully and provide an existing roof framing plan showing connection of the new PV panels. Please provide connection details to the existing framing.
03/29/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied PROJECT; T10CM00516
2030 E Speedway
Solar Photovoltaic Installation

The electrical plans for this project have been denied for the following:

1. The 400 amp 120/240 volt 3 phase 4 wire delta service shows 6 main disconnects, the Photovoltaic service will be the 7 th. How will this comply with NEC 230.71 ?
2. Show the size and run from the GEC at main service to each Inverter, per NEC 690.47.
3. The Main disconnect for the Photo Voltaic system is to be shown in reference to the CT enclosure.

Ray T Majuta
PDSD, C of Tucv
3/29/10
Ray.Majuta@tucsonaz.gov
03/30/2010 PAUL MACHADO ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/06/2010 CPIERCE1 OUT TO CUSTOMER Completed
04/06/2010 SUE REEVES REJECT SHELF Completed