| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/19/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
| 03/26/2010 | RONALD BROWN | ZONING HC | REVIEW | Passed | |
| 03/26/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | Please provide structural calculations for the additional load added to the existing roof framing system. Decsribe fully and provide an existing roof framing plan showing connection of the new PV panels. Please provide connection details to the existing framing. |
| 03/29/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PROJECT; T10CM00516 2030 E Speedway Solar Photovoltaic Installation The electrical plans for this project have been denied for the following: 1. The 400 amp 120/240 volt 3 phase 4 wire delta service shows 6 main disconnects, the Photovoltaic service will be the 7 th. How will this comply with NEC 230.71 ? 2. Show the size and run from the GEC at main service to each Inverter, per NEC 690.47. 3. The Main disconnect for the Photo Voltaic system is to be shown in reference to the CT enclosure. Ray T Majuta PDSD, C of Tucv 3/29/10 Ray.Majuta@tucsonaz.gov |
| 03/30/2010 | PAUL MACHADO | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/06/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 04/06/2010 | SUE REEVES | REJECT SHELF | Completed |