Permit Number: T10CM00513
Parcel: 126062750

Address:
612 N TEXAS CI

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T10CM00513
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2010 RONALD BROWN BUILDING-RESIDENTIAL REVIEW Denied FLOOR PLANS:
1. Please show the location of attic access min. 22"x30", R807.
FOUNDATION PLANS:
2. Please provide a note for termite treatment, R320 as amended.
SECTIONS - DETAILS:
3. Please specify wall and ceiling covering. Note: Ceiling gypsum board must be either 5/8" or ½" SAG RESISTANT
when applied to ceilings framed at 24” o/c, IRC table R702.3.5 footnote d.
ELECTRICAL PLANS:
4. Please clarify your electrical riser diagram. Please provide a total house plan showing showing all existing meters, electrical drops, and panels. Please show what panels are to be replaced, what panels are new and or relocated. Please coordinate the Panel Labeling. Please indicate the panel/s that will feed the existing circuits and there location. Please indicate junction boxes that are to replace a removed panel if there are any.
a. Provide an electrical riser diagram with grounding method and bonding to metallic piping, E3303,
E3507. Show an underground service entrance on the Riser Diagram or complete the Underground
Electrical Service Wavier form.
b. Provide riser diagrams for sub-panels with feeder conductors, conduit sizes, and over-current
protection (with appropriate correction factors), E3605.5.
c. Provide equipment rated for 22,000 AIC short circuit protection when the underground cable length is
less than 45 feet, 2006 Electric Service Requirements TEP SR-510.
d. Provide electrical load calculations for determining the service panel size, E3502.2.
e. Provide feeder load calculations for sub-panels (40% demand factor may not be applied), E3604.3.
f. Provide a panel schedule: panel size, circuit numbers, ampacity, and wire sizes, E3304.11, E3606.2.
g. Provide a panel schedule: panel size, circuit numbers, ampacity, and wire sizes, E3304.11, E3606.2.
MECHANICAL PLANS:
5. Show supply and return ducts with minimum R-8 insulation, R1103.2.1.
6. Show the condensate line and secondary for HVAC unit, M1411.3.
INTERNATIONAL ENERGY CONSERVATION CODE:
7. Provide a note requiring the insulation certificate shall be posted in the electrical distribution panel before final inspection, N1101.8.
END OF INSPECTION