Permit Number: T10CM00463
Parcel: 11706187D

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T10CM00463
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2010 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: ANcongress
T10CM00463
Site Plan (2nd Review)

TRANSMITTAL DATE: July 13, 2010

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC). This project has been reviewed for full code compliance for the areas of expansion and modification to the existing parking and loading area.

2. At the northeast corner of the building there is a building overhang that encroaches into the right-of-way. Contact Jim Rossie, COT Real Estate, (520) 837-6718 in regards to Temporary Revocable Easement (TRE) requirements.

3. For both the DRB and MDR provide information as to what was approved or waived and any conditions of approval on the plan adjacent to the DRB and MDR numbers and approval dates.

4. D.S. 2-02.2.2.A.4 Per the MDR the required number of vehicle parking spaces is 61. Revise the parking calculation to show 61 vehicle parking spaces required per MDR-10-01, 61 vehicle parking spaces provided.
5. D.S. 2-02.2.2.A.5 The northern most loading space shown on the plan appears to encroach into an existing "IRON FENCE". Based on the MDR only one (1) loading space is required, remove the northern most loading space from the plan.
6. Once the above comments have been address Zoning is available for an over-the-counter review. Please call or email to schedule an appointment..
If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t10cm00463

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents.
07/16/2010 RONALD BROWN HC REVIEW Denied 1. OK
2. OK
3. Both groups of accessible parking spaces must have a marked crossing compliant with ICC (ANSI) 117.1, Sections 106, 406.12 and 406.13. Please provide a large scale detail of both crossings showing all critical accessible requirements for code compliance.
RESUBMITTAL COMMENTS:
a. Please provide a detectable warning strip in both groups of accessible parking in the aisle just prior to entering the PAAL.
b. At the Most Westerly group of accessible parkings spaces, a separation of the accessible route and parking aisles adjacent to the parking spaces and the PAAL will be required by Zoning. Reference Zoning comments for the accepted types of separation. A 6" surface mounted curb will work just fine.

4. Please provide a large scale detail of the exact parking design as shown on the site plan showing all critical accessible requirements per code compliance. Generic details such as 4/A1.1 are not acceptable.
RESUBMITTAL COMMENTS:
a. Detail 8/A1.3 is not the same as the parking layout shown on sheet A1.2

5. OK

6. Please provide a large scale detail of the accessible parking sign including a "Van Accessible" sign.
RESUBMITTAL COMMENTS
a. Detail 5/A1.3 does not show a "Van Accessible" sign.
b. Please shjow a large scale detail of the Accessible parking signage required and show a "Van Accessible" sign below the main sign. The main sign is to be no lower than 7' above finishe grade.
c. Please show all sign locations on sheet A1.2.

7. OK

8. Please detail all stairs, treads, risers and railing systems.
RESUBMITTAL COMMENTS
a. I see no handrail detail at the steps leading up to the elevator level and main South Entrance.

9. At all stairs please insure vertical clearance compliance
as per Section 307.4.
RESUBMITTAL COMMENT
a. Please clarify Stair #2, West side, compliance with vertical clearance as per ICC (ANSI 117.1), Section 307.4.

END OF REVIEW
07/16/2010 ANDREW CONNOR LANDSCAPE REVIEW Denied Prior to landscape approval stamp:

Include with re-submittal DRB, RND & HPZ approval documentation. Indicate on the lower right hand corner of the site plan any conditions imposed by the various reviews.

Ensure that all Zoning comments and concerns are addressed
07/19/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/30/2010 PAUL MACHADO ENGINEERING REVIEW Denied To: Miguel Fuentevilla DATE: July 30, 2010
2810 E. 4th Street
Tucson, Arizona 85716

Subject: NAcongress, 278 E. Congress Street
Site plan T10CM00463 (Second Review)
T14S, R13E, Section 12

RESUBMITTAL REQUIRED: Site Plan

The Site Plan (SP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10. The SVT shown are not correct and parking spaces cannot be located in the SVT's. Revise as required.
3. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19. Congress St. is a MS&R designated street. Revise as required.
4. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21. Congress Street included.
5. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. The enclosure can not be accessed traveling the opposite direction one a one way paal. Revise as required.

Drainage Statement:
1. The DS has been accepted by engineering.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/278 E Congress St._Site 2