Permit Number: T10CM00441
Parcel: 10609043B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00441
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2010 GBONILL1 PLUMBING-COMMERCIAL REVIEW Needs Review
02/25/2010 GBONILL1 MECHANICAL-COMMERCIAL REVIEW Needs Review
02/25/2010 GBONILL1 WWM REVIEW Needs Review
02/26/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET a1.1; RESTROOM BUILDING FLOOR PLAN: PER ADAAG SECTION 4.1.3 (10), A HIGH/LOW DRINKING FOUNTAIN IS REQUIRED. PROVIDE.
2. SHEET a1.1: PROVIDE A REFERENCE ON THE DRAWINGS TO ALL APPLICABLE CODES AND REGULATIOLNS USED FOR THIS PROJECT PER IBC SECTION 106.1.1.
3. SHEET S1.1 (DETAIL 26); STRUCTURAL CALCULATIONS (PAGE 34): THE CALCULATIONS INDICATE A FOOTING DEPTH OF 12", WHILE THE DETAIL INDICATES 10". CLARIFY.
4. SHEET S2.0 (FRAMING PLAN); STRUCTURAL CALCULATIONS (PAGE 7): THE LINTEL DLT1 IN THE CALCULATIONS INDICATES A 16" BOND BEAM, WHILE THE FRAMING PLAN INDICATES A DOUBLE ANGLE (PLAN NOTE 10). CLARIFY.
5. SHEET L1.1: GROUND SURFACES ALONG THE ACCESSIBLE ROUTE SHALL MEET ADAAG SECTION 4.5 (DECOMPOSED GRANITE IS REFERENCED).
6. THE ACCESSIBLE ROUTE SHALL MEET THE REQUIREMENTS OF ADAAG SECTION 4.3., INCLUDING SLOPE. VERIFY.
7. SHEET L1.2; DETAILS 4 AND 5: PROVIDE STRUCTURAL CALCULATIONS FOR THE BACKSTOP FRAMING AND FOUNDATION.
8. GENERAL: ALL DEFERRED SUBMITTALS MUST BE APPROVED BY LEERAY HANLY BEFORE A PERMIT WILL BE ISSUED.
9. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/02/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/15/2010 CPIERCE1 OUT TO CUSTOMER Completed
03/15/2010 SUE REEVES REJECT SHELF Completed