Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10CM00440
Parcel: 14026045A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM00440
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SEE PREVIOUS COMMENT: PER STRUCTURAL CALCULATION ON SHEET 5 FOR BEAMS SUPPORTING EVAPORATIVE COOLERS, A 4X8 IS REQUIRED. SHEET M2.0 (EVAP. COOLER MOUNTING DETAIL) INDICATES A 4X4 BEAM. REVISE.
03/04/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Wet venting the urinal and the floor drain will require a 3" wet vent between the urinal and the floor drain. Reference: Section 908.2, UPC 2006.
2. Provide a method for priming the floor sink by office 168. Reference: Sections 1007.0 and 1007.1, UPC 2006, as amended by the City of Tucson.
3. The branch piping sizes called out for the urinal flush valves will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Sections 610.12 and A 6.1, UPC 2006 and IS 3-2003, Section 2.6.
03/04/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/05/2010 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/05/2010 DELMA ROBEY OUT TO CUSTOMER Completed