Permit Number: T10CM00440
Parcel: 14026045A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00440
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2010 STEVE SHIELDS ZONING REVIEW Approved
02/23/2010 BIANCA RAMIREZ ENGINEERING REVIEW Approved
02/23/2010 ERIC NEWCOMB ADA REVIEW Passed
02/23/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PER STRUCTURAL CALCULATION ON SHEET 5 FOR BEAMS SUPPORTING EVAPORATIVE COOLERS, A 4X8 IS REQUIRED. SHEET M2.0 (EVAP. COOLER MOUNTING DETAIL) INDICATES A 4X4 BEAM. REVISE.
02/23/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
02/23/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/24/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Condensate drains (PTAC) may not terminate in an area not capable or absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson.
02/24/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a floor drain in the restroom. Reference: Section 411.2, UPC 2006.
2. Show that the floor of the restroom slopes toward the floor drain. Reference: Section 411.2, UPC 2006.
02/24/2010 ROBERT SHERRY WATER REVIEW Approved
02/25/2010 DAVE MANN FIRE REVIEW Approved
02/25/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/04/2010 CAGUILA1 WWM REVIEW Needs Review