Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM00440
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/23/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
02/23/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
02/23/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
02/23/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PER STRUCTURAL CALCULATION ON SHEET 5 FOR BEAMS SUPPORTING EVAPORATIVE COOLERS, A 4X8 IS REQUIRED. SHEET M2.0 (EVAP. COOLER MOUNTING DETAIL) INDICATES A 4X4 BEAM. REVISE. |
02/23/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
02/23/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
02/24/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Condensate drains (PTAC) may not terminate in an area not capable or absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson. |
02/24/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a floor drain in the restroom. Reference: Section 411.2, UPC 2006. 2. Show that the floor of the restroom slopes toward the floor drain. Reference: Section 411.2, UPC 2006. |
02/24/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
02/25/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
02/25/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
03/04/2010 | CAGUILA1 | WWM | REVIEW | Needs Review |