Review Details: COMMERCIAL TI

Permit Number - T10CM00400
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2010 DAVE MANN FIRE REVIEW Denied Fire Comments:

Sheets PIIG3.0 and E3.1
No new exit signs are shown. Please clarify if existing exit signs are to be used. Coordinate with exit plan on PIIG3.0. Some doors that appear to be exits are not used on the plan.

SheeA6.2
Describe the use of the BBQ. If used inside the building it needs a hood and supression system. If for outside use an LP tank cannot be rolled back into the building.
02/22/2010 SREEVES1 ADA REVIEW Passed
02/23/2010 GERRY KOZIOL WWM REVIEW Approved
02/23/2010 SUE REEVES COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/23/2010 ELIZABETH LEIBOLD ENGINEERING REVIEW Approved
02/24/2010 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the size of the existing water meter and the total connected water demand that will result from the addition of this activity. Reference: Sections 610.1 and 610.2, UPC 2006. 2. Supply water isometrics, include location and type of water hammer arrestors. Reference: 103.2.3 2006 UPC. 3. Provide calculations showing how the water supply piping has been sized. Reference: Sections 610.4 and 610.5, UPC 2006. 4. Include how the domestic water is to be sterilized. Reference: 609.9 2006 UPC.
02/24/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the use of room 348 on sheet PIIA2.1 (the same space is noted as room 345 on sheet PIIA6.2), is it a "Break Room" or a "Cafeteria"? If food will be sold, show that the appropriate documents have been submitted to the Pima County Health department for review.
2. Clarify the nature of the "BBQ GRILL (WITH WHEELS)" shown on PIIA6.2, keynote 12. Reference: Sections 106.3.1 and 507.2 IMC 2006.
3. Clarify the applicability of note 12 in the "Variable Air Volume Terminal Unit" schedule on sheet M0.1. Show how the revised VAV system is capable of maintaining a minimum temperature of 68 F in the interior spaces intended for occupancy on a design heating day (32 F). Reference: Sections 309.1 and 312.1, IMC 2006.
4. Provide calculations demonstrating adequate ventilation. Reference: Section 401.2, IMC 2006.
5. Show the balancing information for the existing diffusers, the new diffusers and for the exhaust fans. Reference: Sections 106.3.1 and 403.3.4, IMC 2006.
6. Clarify the "Sequence of Controls" information shown on sheet M0.0. Reference: Section 106.3.1, IMC 2006.
7. Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (3), IMC 2006.
8. Section 507.2.2, exception 3, IMC 2006 allows for a single microwave oven to be installed without a Type II hood. Sheet PIIA6.2 indicates that a bank of four microwave ovens will be installed. Provide a Type II exhaust hood for the microwave ovens. Reference: Section 507.2, IMC 2006.
9. Materials exposed in plenums shall conform to Section 602.2.1, IMC 2006.
02/24/2010 RMYERS1 WATER REVIEW Denied 1.14. Provide site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 103.2.3, UPC 2006.
02/25/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) pp PIIG1.0
You are showing 66,800 s.f. of area with an allowable of only 9,000 s.f. Please justify area increase.

2) pp PIIG3.0
Please clarify exit signage and coordinate exit signage with pp E3.1 and E3.2.

3) pp PIIA6.1
a) Details 1 & 2 show vertical grab bars at 38" from rear wall; correct dimension is is 39" - 41".
b) Please clarify (dimension) the locations of the shower controls and fold-up seat in reference to the finished surfaces.

3) pp PIIA6.2
a) Please coordinate your room #'s with pp PIIA2.1.
b) Keynote 12 -- BBQ inside a building? Please coordinate fuel and hood requirements with mechanical plans.
c) You are showing a bank of 4 microwave cookers. Please show required type II hood and coordinate with mechanical sheets.

4) PIIA10.1
Details 1 & 2 refer to "no-flex" details. Where are the "no-flex" details.
02/25/2010 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Denied Electric plans denied for the following:

1. Provide information on exit signs. None indicated on plans.

2. If Type II hood to be installed per mechanical review comments need to indicate circuiting.

3. Is Type I hood being installed for BBQ shown in break rm? If so provide circuiting & electric schematic of control system.

Rich Jiroudek
Electic Plns Exmn
520-954-0161
02/25/2010 LEERAY HANLY ZONING HC REVIEW Approved
02/26/2010 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: T10CM00400
3470 E. Universal Wy.
TI: Office

TRANSMITTAL DATE: 02/26/10

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Per review of the last approved development plan (D98-061) the amount of provided parking spaces for the entire site is 291 parking spaces. The provided plan for the office tenant improvement indicates the building area as 66,800 sq. ft. Per LUC Sec. 3.3.4 the required parking for an office use is one parking space per 200 sq. ft. of gross floor area. The total number of required parking spaces for this office use is therefore 334 parking spaces. An additional 43 parking spaces are required.

A revised development plan or board of adjustment variance would be required in order for the zoning section to approve this use on the proposed site.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\T10CM00400.doc

Final Status

Task End Date Reviewer's Name Type of Review Description
03/05/2010 SUE REEVES OUT TO CUSTOMER Completed
03/05/2010 SUE REEVES REJECT SHELF Completed