Permit Number: T10CM00395
Parcel: 106041250

Address:
413 E MOHAVE RD

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/NPPO

Permit Number - T10CM00395
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2010 BEVERLEY HESTER ENGINEERING REVIEW Denied Date: June 11, 2010
Activity #: T10CM00395
Review: First
Project Location: 413 E. Mohave Rd.
Review Type: Engineering - Site Plan
Reviewer: Beverley Hester

Summary of Review
This review is from the Planning and Development Services Department's Engineering Division for the site plan only. A re-submittal is required. Please include a response letter to the comments detailed below in your next submittal. The floodplain use permit review is an engineering review that is related to this review and the comments are, or will be, posted separately under Activity # T10OT00418. This permit will not be approved until the floodplain use permit is approved.

Site Plan Comments from "City of Tucson Development Standard No. 2-02.0 Site Plan Content and Specifications"
2.1.7. Please show distances between buildings dimensioned.
2.1.15. Please show limits of the 100-year floodplain and water surface elevations. A statement on the plans identifying the type of floodzone(s) is acceptable.

The site plan did not accurately depict the access location or the fence lines. The site plan did not accurately depict the access location or the fence lines. Please show the access location, along with the sidewalk area, curb cut location and the distance from the driveway to existing adjacent property driveways.

If you have any questions or would like to discuss this project, please don't hesitate to contact me.

Respectfully,
Beverley Hester

City of Tucson
Planning and Development Services Department
Engineering Division

201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210

Bev.Hester@tucsonaz.gov
(520) 837-4935 office
(520) 879-8010 fax
06/11/2010 GERRY KOZIOL WWM REVIEW Passed
06/30/2010 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T10CM00395

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
Show corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007 and the 2006 UPC with amendments on 7/10/2007. For initial construction: Effective 1/1/2007 the Inclusive Home Design; starting 3/1/2009 Solar Water Preparation and 7/1/2009 Solar Photo-Voltaic Preparation are required for all new SFR and duplex plans. Show the code references on the plans. Amendments to adopted codes are at the City web-site http://www.tucsonaz.gov: Planning, Building, & Business; under the Building topic; Building Ordinances and Codes; Building Codes

FOUNDATION PLANS:

1. Provide a landing or floor surface at all exterior doors. A landing must be at least as wide as the door it serves and 36" in the direction of travel, R311.4.3.
2. Clarify the plans showing a continuous minimum 12" deep footing at all exterior walls, R403.1.

FLOOR PLANS:

1. Revise the floor plan showing an opening or doorway between the Kitchen and Dining Room, R106.1.1.
2. Show compliance with R303.1 providing (8%) natural light and (4%) natural ventilation into the Dining room.

MECHANICAL PLANS:

1. Show supply and return ducts with minimum R-8 insulation (includes vented attics) except when completely located inside the thermal envelope, R1103.2.1.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review