Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM00365
Parcel: 110113610

Address:
2490 N SWAN RD

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T10CM00365
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2010 DAVE MANN FIRE REVIEW Approved Separate, deferred submittal for underground fuel storage tanks required through Fire department.
02/25/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide structural calculation for foundation.
02/25/2010 RONALD BROWN ZONING HC REVIEW Approved
03/02/2010 ANDREW CONNOR ZONING REVIEW Denied 03/02/2010

Development Services Department
Zoning Review Section

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.
03/03/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM00365, 2480 N Swan Rd,
New Fuel Center Kiosk,


The Electrical Plans have been denied for the following:

1. Provide load calculations on SES-B which will show existing and new load being added by this project.
2. Show compliance with current City of Tucson Outdoor Light Ordinance # 10135. Can be found on City of Tucson Web page.
3. Provide a cut sheet of all fixtures being installed.

Ray T Majuta, Elect Plan Review
DPDS< City of Tucson,
3/05/10,
Ray.Majuta@tucsonaz.gov
03/05/2010 RICK MYERS PLUMBING-COMMERCIAL REVIEW Passed
03/05/2010 RMYERS1 WATER REVIEW Passed
03/10/2010 GERRY KOZIOL WWM REVIEW Passed
03/12/2010 LOREN MAKUS ENGINEERING REVIEW Denied The Development Plan must be approved before the building plan is approved.
03/18/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide energy code compliance calculations (if COMcheck is used, the climate zone is Pima County < 4,000 feet). Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
2. Show that the condensate trap for the air conditioning unit has been designed in accordance with the manufacturer's installation instructions. Reference: Section 304.1, IMC 2006.
3. Show the routing and termination of the condensate drain. Condensate drains shall terminate with an air break over an indirect waste receptor or shall terminate in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/26/2010 CPIERCE1 OUT TO CUSTOMER Completed
07/26/2010 SUE REEVES REJECT SHELF Completed