Permit Number: T10CM00364
Parcel: 110113610

Address:
2490 N SWAN RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM00364
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Section 1101.12.2, UPC 2006 requires a cleanout at the base of each roof drain leader prior to its connection with the horizontal storm drain. If there is a structural reason why this cannot be done, submit an Appeal to the Building Official stating how the proposed alternate location at the base of the column will result in equivalent effectiveness. Include a detail on the drawing (e.g. C-2) clearly showing the proposed location for the cleanout. Reference: Section 301.2, UPC 2006.
08/25/2010 LOREN MAKUS ENGINEERING REVIEW Denied The Development Plan must be approved before the building plans are approved.
08/30/2010 DAVID RIVERA ZONING REVIEW Denied See related zoning comments under Activity number T10CM000365 for reference of denial and approval.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/07/2010 DELMA ROBEY OUT TO CUSTOMER Completed
09/07/2010 SUE REEVES REJECT SHELF Completed