Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM00358
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/16/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | Needs to install sprinkler system or provide an exit door to outside from each classroom. |
02/16/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The installation of a range in a commercial building will require a Type I hood with make up air. 2. Provide calculations to show that the ventilation is adequate for the new use. Reference: Section 403, IMC 2006. |
02/16/2010 | RONALD BROWN | ADA | REVIEW | Passed | |
02/16/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
02/16/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
02/16/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide receipt from Pima County Health Department prior to the plumbing review. |
02/16/2010 | RONALD BROWN | ZONING HC | REVIEW | Approved | |
02/24/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
02/24/2010 | CRAIG GROSS | ZONING | REVIEW | Approved | |
02/24/2010 | CPIERCE1 | ENGINEERING | REVIEW | Needs Review | |
02/24/2010 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
02/24/2010 | CPIERCE1 | FIRE | REVIEW | Needs Review |