Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2010 GERRY KOZIOL WWM REVIEW Approved
02/23/2010 LHANLY1 BUILDING-RESIDENTIAL REVIEW Denied 1) SPECIFY HOW WEIGHT OF FURNACE AND HOW IT IS TO BE SUPPORTED IN ATTIC.

2) 24" WIDE PATH TO FURNACE, WORK-LIGHT AND PLUG RECEPTACLE REQUIRED FOR FURNACE.

3) GAS DEMAND FOR FURNACE GIVEN AS 75000 BTU WHILE FURNACE IS LISTED AS 80000 BTU. PLEASE COORDINATE.

4) PLEASE PROVIDE GAS ISOMETRIC.

5) PLEASE INDICATE HOW THE TPRV DISCHARGE LINE FROM THE WATER HEATER IS GOING TO BE RUN TO THE EXTERIOR OF THE HOME.

6) PLEASE INDICATE HOW YOU WILL PROVIDE EXHAUST VENTILATION FOR THE BATHROOM AND POWDER ROOM.