Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM00316
Parcel: 114462090

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T10CM00316
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2010 Michael Wyneken PLANNING-CITY HALL REVIEW Approved
02/17/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM0031446, 7871 E Wrightstown Rd



Provide locations of other electrical services providing power to existing monopole, show on electrical sheet.

Ray T Majuta, DSPD, City of Tucson
Elect Pln Ck , 2/18/10
Ray.Majuta@tucsonaz.gov
02/22/2010 BRIAN HEFFERNAN COMMUNICATIONS REVIEW Approved
02/24/2010 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T10CM00316 Cell Tower (1st Review)

TRANSMITTAL DATE: February 24, 2010

1. The Cell Tower plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning has reviewed the plan and it appears that it meets all LUC and D.S. requirements. Once all PDSD agencies have approved the plan Zoning will approve the plan.

3. Zoning will re-review the Cell Tower plan on the next submittal to insure compliance with the approved Special Exception process. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\celltower\t10cm00316.doc
03/05/2010 ELIZABETH EBERBACH ENGINEERING REVIEW Approved
03/09/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/10/2010 CPIERCE1 OUT TO CUSTOMER Completed
03/10/2010 SUE REEVES REJECT SHELF Completed