Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM00300
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/18/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
02/19/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
02/22/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide sufficient information on the gas piping system for evaluation of the proposed changes. Provide a natural gas piping design, including the piping layout on a floor plan showing the sizes, loads and developed lengths of the piping. Reference: Sections 101.5.1, 103.2.3, and 1217.0, UPC 2006. 2. Clarify Section 3.01 of the mechanical specifications with regard to the support spacing. Reference: Tables 3-2 and 13-7, UPC 2006. 3. Provide special inspection form for medical gases. |
02/22/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify the basis for using 0.12 CFM/SF for the animal areas. ASHRAE 62-1-2004, Table 6-1 calls for using a ventilation rate based on a default occupant density of 10 people and a combined outdoor air rate of 26 CFM/person. Reference: Section 403.2, IMC 2006, as amended by the City of Tucson. 2. Provide calculations verifying compliance with requirements for medical gas storage rooms, including mechanical exhaust of the enclosure and a 1-hour shaft for the exhaust duct. Reference: Sections 501, 502.8, and 502.9, IMC 2006 and, Section 3006, IFC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/08/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
03/08/2010 | SUE REEVES | REJECT SHELF | Completed |