Permit Number: T10CM00300
Parcel: 10821018Y

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00300
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/18/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/19/2010 GERRY KOZIOL WWM REVIEW Approved
02/22/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide sufficient information on the gas piping system for evaluation of the proposed changes. Provide a natural gas piping design, including the piping layout on a floor plan showing the sizes, loads and developed lengths of the piping. Reference: Sections 101.5.1, 103.2.3, and 1217.0, UPC 2006.
2. Clarify Section 3.01 of the mechanical specifications with regard to the support spacing. Reference: Tables 3-2 and 13-7, UPC 2006.
3. Provide special inspection form for medical gases.
02/22/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the basis for using 0.12 CFM/SF for the animal areas. ASHRAE 62-1-2004, Table 6-1 calls for using a ventilation rate based on a default occupant density of 10 people and a combined outdoor air rate of 26 CFM/person. Reference: Section 403.2, IMC 2006, as amended by the City of Tucson.
2. Provide calculations verifying compliance with requirements for medical gas storage rooms, including mechanical exhaust of the enclosure and a 1-hour shaft for the exhaust duct. Reference: Sections 501, 502.8, and 502.9, IMC 2006 and, Section 3006, IFC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/08/2010 CPIERCE1 OUT TO CUSTOMER Completed
03/08/2010 SUE REEVES REJECT SHELF Completed