Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10CM00298
Parcel: 13322471B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00298
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/17/2010 TERRY STEVENS ZONING REVIEW Approved
02/17/2010 ROBERT SHERRY WATER REVIEW Approved
02/17/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/17/2010 MARTIN BROWN FIRE REVIEW Approved
02/17/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/17/2010 GERRY KOZIOL WWM REVIEW Approved