| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/09/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/09/2010 | LEERAY HANLY | MECHANICAL-COMMERCIAL | REVIEW | Denied | EF-1 FANS ARE UNDERSIZED FOR EXHAUSTING SUPPLY AIR BEING PROVIDED TO RESTROOMS. MECHANICAL PAGES INDICATE A TIME CLOCK SHALL BE INSTALLED SO THAT EF-1 FANS ARE ON WHILE BUILDING IS OCCUPIED, BUT ELECTRICAL PAGES SHOW THEM BEING SWITCHED. |
| 02/09/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/09/2010 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 02/09/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/09/2010 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. All fixure traps require vents. Reference: 901.0 2006 UPC. See sheet P-1 detail five; floor sink. 2. Include how the water is to be sterilized. Reference: 609.9 2006 UPC. 3. Show the size of the grease trap. A hydo mechanical grease interceotor will require a vented flow control device installed in a visible, and readily accessible location. 4. See sheet P-1, detail four- electric water heater. Include heat traps or heat trap fittings, when using 2006 IECC requirements for insulating first eight feet of hot and cold water piping from the water heater. 5. Include water calculations for determaining the sizes of water pipes to all fixtures. Show the pipe sizes to each fixture in the childs restroom. |
| 02/09/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 02/09/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 02/17/2010 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 02/17/2010 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
| 02/17/2010 | CPIERCE1 | WATER | REVIEW | Needs Review | |
| 02/17/2010 | CPIERCE1 | FIRE | REVIEW | Needs Review |