Permit Number: T10CM00288
Parcel: 13821274B

Address:
6944 S 8TH AV

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T10CM00288
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2010 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 5-22-10
Activity: T10CM00288
Address: 6944 S. 8th Ave
Applicant: Guillermo Durazo

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

FLOOR PLANS:
2. Tiled surfaces around tub/shower enclosures require cement or fiber-cement board backing, R307.2, R702.4.2.

FOUNDATION PLANS:
3. All exterior framed walls require continuous concrete footings min. 12"wide x 12" below grade with treated sill plates and anchor bolts per R319.1 & R403.1.6 (including carport and porch enclosures).

PLUMBING PLAN:
4. Provide note requiring that water hammer arrestors be installed in accordance with ASSE 1010-2004 on water lines serving appliances equipped with quick-closing valves to include but not limited to: clothes washers, dishwashers, and refrigerators, UPC 609.10.
5. Provide the maximum developed length of water line from the meter the furthest appliance served, UPC Table 6-6.
6. Provide an accurate fixture unit schedule for the water supply (including existing) UPC Tables 6-5 and 7-3.

MECHANICAL PLAN:
7. Show supply and return air ducts with a minimum R-8 insulation, R1103.2.1.

INTERNATIONAL ENERGY CONSERVATION CODE:
8. Specify the maximum allowable "U" factor and solar heat gain coefficient of the windows and doors that meets or exceeds the requirements of N1102.1. The simplified prescribed energy value for climate zone 2B glazing and skylights is maximum U=0.75, the maximum SHGC is 0.40.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/26/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
05/26/2010 SUE REEVES REJECT SHELF Completed