Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM00279
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/04/2010 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 02/04/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/04/2010 | RICHARD JIROUDEK | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/04/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/04/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/04/2010 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 02/04/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 02/04/2010 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 02/04/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/04/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 02/04/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 02/05/2010 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/12/2010 | SUE REEVES | APPROVAL SHELF | Completed |
| 02/12/2010 | BETH GRANT | OUT TO CUSTOMER | Completed |