12/13/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied PROJECT; T10CM00252
4000 N Sun Tran Bl
Maint Bldg

Concerning Item #1 issues A,B and C, your response indicates that the Pull Box as described on Note 15 (which is to be installed ), however " it is neither necessary or required ", is very confusing. The Inspector will either expect to see one per Note 15, and it should be the responsibility of EE to size it, or Note 15 should be removed.
2. If the feeder to MT-SESA is only a feeder, why would the neutral be connected to Bldg Steel, Water Pipe and Ufer as shown on Sheet4.1E?

Ray T Majuta,
PDSD,City of Tucson,
Elect Pln Ck,
12/14/10