Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM00253
Parcel: 106101650

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM00253
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2010 STEVE SHIELDS ZONING REVIEW Approved
04/26/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/26/2010 ROBERT SHERRY WATER REVIEW Denied Correct the arithmetic used for the water pressure calculations. The permissible friction loss (i.e. the pressure available for friction) is the design pressure less the required static lift, the losses due to the water meter, backflow preventer, and the required residual pressure. See Sections A3.1 through A3.4 for detailed instructions for determining the permissible friction loss. Reference: Sections 608.1, 610.1 and 610.2, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/06/2010 SUE REEVES OUT TO CUSTOMER Completed
05/06/2010 SUE REEVES REJECT SHELF Completed