Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T10CM00252
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/13/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PROJECT; T10CM00252 4000 N Sun Tran Bl Maint Bldg Concerning Item #1 issues A,B and C, your response indicates that the Pull Box as described on Note 15 (which is to be installed ), however " it is neither necessary or required ", is very confusing. The Inspector will either expect to see one per Note 15, and it should be the responsibility of EE to size it, or Note 15 should be removed. 2. If the feeder to MT-SESA is only a feeder, why would the neutral be connected to Bldg Steel, Water Pipe and Ufer as shown on Sheet4.1E? Ray T Majuta, PDSD,City of Tucson, Elect Pln Ck, 12/14/10 Ray.Majuta@tucsonaz.gov |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/28/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
12/28/2010 | SUE REEVES | REJECT SHELF | Completed |