Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM00252
Parcel: 106101650

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T10CM00252
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/13/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied PROJECT; T10CM00252
4000 N Sun Tran Bl
Maint Bldg

Concerning Item #1 issues A,B and C, your response indicates that the Pull Box as described on Note 15 (which is to be installed ), however " it is neither necessary or required ", is very confusing. The Inspector will either expect to see one per Note 15, and it should be the responsibility of EE to size it, or Note 15 should be removed.
2. If the feeder to MT-SESA is only a feeder, why would the neutral be connected to Bldg Steel, Water Pipe and Ufer as shown on Sheet4.1E?

Ray T Majuta,
PDSD,City of Tucson,
Elect Pln Ck,
12/14/10
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
12/28/2010 CPIERCE1 OUT TO CUSTOMER Completed
12/28/2010 SUE REEVES REJECT SHELF Completed