Permit Number: T10CM00252
Parcel: 106101650

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T10CM00252
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM00252,
4000 N Sun Tran Bl
Maint Bldg

The electrical plans have been denied for the following:

1. Sheet E4.1, concerning notes 13,14,and 15, please provide the following information for clarity of review and installation:

A. provide a detail showing location of new pull box,show how 4" conduits to enter and leave the pull box,provide a description of the box showing height,depth and width.Will conductors be spliced or run through. If spliced what materials are to be used?
B. If the existing 4" conduits are to be interupted, how will pull box be set to intercept the conduits?
C. Will pull box be in the ground or supported on a surface?
D. If neutral is not needed now and is to be coiled in the transformer and the panel , why is it being installed? What could be a possibility of using it at a later time?
E. Concerning the conductors from the transformer to the new MTSESA board, show how the installation complies with NEC 2005, 240.21.C.2.
F Indicate on Sheet E4.1, the equipment connected to the circuits on MTSESA.
G. Sheet E4.3,describe the extent of changes(delta 3), on this sheet. Since previous approved plans not provided, or provide electrical sheets only.
H. Regarding the changes to the panel schedules, provide information as to why the changes are made.

Ray T Majuta,
PDSD, City of Tucson,
Elect Plan Ck,
10/20/10