Permit Number: T10CM00252
Parcel: 106101650

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM00252
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2010 DAVE MANN FIRE REVIEW Approved
04/12/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/14/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved; the pressure drop due to the water meters and the reduced pressure backflow preventer has not been included correctly in the calculations. See Sections A3.1 through A3.4 for detailed instructions for determining the permissible friction loss. Reference: Sections 608.1, 610.1 and 610.2, UPC 2006.
2. Comment not resolved. If the size of the scuppers and the conductor overflow openings shown on detail 13/A8.5.1 are correct, many of the scuppers and the conductor overflow opening are too narrow; roof areas greater than 2147 square feet require a minimum scupper width of 12.6 inches. It is also not clear how the roof sections served by scuppers will be provided with overflow protection. See the sizing criteria in Section 1101.11.2.1, UPC 2006. Reference: Section 1101.11, UPC 2006.
04/19/2010 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Sun Tran Expansion
T10CM00251, T10CM00252, T10CM00253
Building Plan (3rd Review)

TRANSMITTAL DATE: April 19, 2010

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning has reviewed the building plans and it appears they match the development package. Zoning will stamp and approve the building plans once all PDSD agencies have approved the plans.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped Development Package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
04/19/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/21/2010 SUE REEVES OUT TO CUSTOMER Completed
04/21/2010 SUE REEVES REJECT SHELF Completed