Permit Number: T10CM00236
Parcel: 107020070

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00236
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
01/28/2010 BIANCA RAMIREZ ENGINEERING REVIEW Approved
01/29/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Need Energy lighting budget calculations per IECC 2006.

Ray T Majuta
Elect Pln CK
520-837-4988
1/29/10
01/29/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/29/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. need structrual calculations for:
A. Roof mounted HVAC unit
b. Water heater mounting
c. suspended electrical transformer
2. See Jesus for other comments
01/29/2010 ROBERT SHERRY WATER REVIEW Approved
01/29/2010 RONALD BROWN ZONING HC REVIEW Denied 1. Drinking foundation not accessible
2. Need accessible recptionest counter
3. See Jesus for other items
01/29/2010 DAVE MANN FIRE REVIEW Approved
01/29/2010 RONALD BROWN ADA REVIEW Passed NOT A COT OWNED/OPERATED PROJECT
01/29/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
02/01/2010 GERRY KOZIOL WWM REVIEW Approved
02/01/2010 CPIERCE1 PLUMBING-COMMERCIAL REVIEW Needs Review