Review Details: COMMERCIAL TI
Permit Number - T10CM00236
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/28/2010 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 01/28/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 01/29/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Need Energy lighting budget calculations per IECC 2006. Ray T Majuta Elect Pln CK 520-837-4988 1/29/10 |
| 01/29/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/29/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. need structrual calculations for: A. Roof mounted HVAC unit b. Water heater mounting c. suspended electrical transformer 2. See Jesus for other comments |
| 01/29/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/29/2010 | RONALD BROWN | ZONING HC | REVIEW | Denied | 1. Drinking foundation not accessible 2. Need accessible recptionest counter 3. See Jesus for other items |
| 01/29/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
| 01/29/2010 | RONALD BROWN | ADA | REVIEW | Passed | NOT A COT OWNED/OPERATED PROJECT |
| 01/29/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 02/01/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 02/01/2010 | CPIERCE1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review |